AEG PROTECT 1.100 Power Supply User Manual


 
41
Energiefluss bei gestörtem Netz Power circuit with faulty mains supply
Handumgehungspfad Manual bypass path
Netz Mains
GR REC
EUE SBS
WR INV
Netzeingangssicherungsautomat Mains input miniature circuit breaker
Lade GR Load REC
Handumgehung Manual bypass
Gesicherte Schiene Secured busbar
Schematische Darstellung Schematic diagram
Batterie Battery
Verbraucher Load
The mains is not within the required tolerance range or has
failed. In this case, power is supplied to the inverter from the
charged battery without interruption. The power supply to the
loads is therefore also ensured in the event of a mains failure.
This drains the capacity of the battery and it is discharged. This
status is signalled by the battery symbol lighting up (Battery
LED), as well as an intermittent acoustic signal, at first every 4
seconds and then every second shortly before switching off.
The initial alarm can be suppressed by pressing the “Alarm off”
button. The alarm is automatically reactivated when the battery
capacity decreases. Depending on the expansion level, age
and condition of the battery and in particular on the load to be
supplied, the standby time can vary from a few minutes to
several hours.
The inverter is switched off if the battery voltage drops below a
factory-set minimum voltage value.
Never store the unit in this condition! The discharged battery
system should be recharged within a week at the latest.
When the voltage and frequency are within the tolerance range
again after the mains is restored, the rectifiers switch back on