MX06 Power Plant User’s Manual Page 10
Battery Temperature Probe Installation
The 15 Ft (4.5m) temperature probe is used to monitor the battery string temperature. To get
the most representative temperature measurement, the probe should be placed in contact with a
battery cell that is centrally located. The probe should be placed directly in contact with the cell
(not the frame surrounding the cell). Generally, the cell cover can be used; be careful not to
allow the probe body to touch the terminals. Plug the connector end of the temperature probe
into J4 of the backplane card. Route the cable as required positioning the probe on the selected
battery cell. Remove the adhesive protection strip from the probe body and press the adhesive
side of the probe on the battery cell cover. Refer to Figure 3.4-4 for details. A 50Ft (15m)
temperature probe is also available.
Figure 3.4-4 Battery Temperature Probe Installation
3.5. DC System Grounding
The positive bus for the power plant should be connected to the Central Office Ground. The
Battery Return provides a pair of #10-32 studs on 5/8-inch centers for connection of a two-hole
lugged cable to the Central Office Ground. A ring size of 0.221 in (5.6 mm) may also be used.