American Power Conversion PD60F6FK1 Power Supply User Manual


 
50 60 kW InfraStruXure PDU — Operation and Configuration
How to Add Circuit Breakers and Power
Cables
Add a circuit breaker on the PDU
1. Snap and bolt the new
circuit breaker into a
position on the panel.
2. Remove the
corresponding plastic
blanking plate on the
front panel of the PDU.
Add a power cable to the PDU
Before adding a power cable, add a circuit breaker.
1. Install a strain-relief connector in any
available knockout on the roof of the
PDU.
2. Slide enough of the power cable through
the strain-relief connector to reach the
new circuit breaker.
3. Tighten the strain-relief connector.
Note
If you must install at 20A or 30A power cable in a knockout designed for a 50A power
cable, you must use reducing washers (included) to adjust the size of the hole.
Note
If you are adding a power cable that will attach to a circuit breaker on the bottom circuit
breaker panel, use a non-conductive fish tape to feed the power cable down the
rectangular wireway (chute) in the center of the PDU. This will allow you to easily
access the bottom circuit breaker panel.