American Power Conversion PD60G6FK1 Power Supply User Manual


 
Overview
10 60 kW InfraStruXure PDU—Operation and Configuration
User connection plate
For a description and location of the user connection plate, see () on page 6. For clarity, the
following illustration shows the user connection plate in greater detail.
Connect the InfraStruXure PDU to the network or the InfraStruXure Manager through the
ethernet port.
The user connection plate has four input contact connections for monitoring Normally Open
(NO) or Normally Closed (NC) dry contacts. See page 20 and page 53 for more information.
The user connection plate has four relay output connections for connection of Normally Open
(NO) or Normally Closed (NC) dry contacts. See page 20 and page 53 for more information.
Connect an Emergency Power Off (EPO) switch at one of three choices of EPO connections
(24VDC, 24VAC, or contact closure). See page 54 for more information.
1 234
ATS EN
ATS 0
ATS 1
ATS 2
EPO
Contact
+
EPO 24V
AC/DC
Contact Inputs
Contact Outputs
USER INTERFACE
© 2001 APC