American Power Conversion PD60G6FK1 Power Supply User Manual


 
18 60 kW InfraStruXure PDU — Operation and Configuration
Contacts Screen
Overview
The PDU can monitor external contact closure events. Possible applications include the following:
Magnetic contact switches
Window foil
Tamper switches
Heat detectors
Water sensors
Pressure sensors
Building smoke and fire detection systems
You can set input contacts to cause alarm conditions based on their current state and a user-defined
normal state. Relay outputs can map internal alarms and events to outside devices. Use the Contacts
screen to display and configure information about input contacts and relay outputs.
Input Contacts Scroll through the list to display information about each of the
installed input contacts. For example, 02of04 displays
information about the second of four installed input contacts.
Name—The name of this contact input (Maximum: 14
alphanumeric characters).
Normal—The normal position of this input contact, either
Open or Closed.
Status—The position of this input contact. If the position is
not the normal position, an alarm condition occurs.
Relay Outputs Scroll through the list to display information about each of the
installed relay outputs. For example, 04of04 displays
information about the fourth of the four available relay outputs.
Name—The name of the relay output (Maximum: 14
alphanumeric characters).
Normal—The normal position of this relay output, either
Open or Closed.
Status—The position of this relay output.
See “Relay Outputs” on page 59 for relay output specifications.