American Power Conversion PD60G6FK1 Power Supply User Manual


 
Overview
60 kW InfraStruXure PDU—Operation and Configuration 7
Rear view of PDU with transformer (interior)
The Main Input switch connects to your main power source. The switch
accepts 208V, 480V, or 600V input and requires 3-wire input conductors.
The PDU monitoring unit has several current and voltage monitoring
boards that report to a central board assembly located in PDU monitoring
unit. The PDU monitoring unit has one 10Base-T (Cat-5) connection to
the Information Controller hub (or switch), four relay output connections,
four input contact connections, and one EPO input connection. Make
these connections at the user connection plate located on the roof of the
PDU.
The delta-wye Input Transformer is based on your input voltage
(208V, 480V, or 600V input). The output of the transformer feeds the
circuit breaker that protects the panel boards.