8 60 kW InfraStruXure PDU—Operation and Configuration
Rear view of PDU without transformer (interior)
The Main Input circuit breaker connects to the main power source
(UPS or utility). The breaker accepts 208V input and requires 4-wire
input conductors.
Note: This circuit breaker also serves as the Main Output (disconnect)
circuit breaker.
The PDU monitoring unit has several current and voltage monitoring
boards that report to a central board assembly located in the PDU
monitoring unit. The PDU monitoring unit has one 10Base-T (Cat-5)
connection to the Information Controller hub (or switch), four relay
output connections, four input contact connections, and one EPO input
connection. Make these connections at the user connection plate located
on the roof of the PDU.
!