AMX NI-2000/3000/4000 Network Card User Manual


 
Terminal (Program Port/Telnet) Commands
99
NI Series WebConsole & Programming Guide
Terminal Commands (Cont.)
Command Description
SET HTTPS PORT Sets the Master’s IP port listened to for HTTPS connections.
Note: The Master must be rebooted to enable new settings.
Example:
>SET HTTPS PORT
Current HTTPS port number = 443
Enter new HTTPS port number (Usually 443) (0=disable HTTPS):
Once you enter a value and press the ENTER key, you get the follow-
ing message:
Setting HTTPS port number to
New HTTPS port number set, reboot the master for the change
to take affect.
SET ICSP PORT Sets the Master’s IP port listened to for ICSP connections.
Note: The Master must be rebooted to enable new settings.
Example:
>SET ICSP PORT
Current ICSP port number = 1319
Enter new ICSP port number (Usually 1319) (0=disable ICSP):
Once you enter a value and press the ENTER key, you get the follow-
ing message:
Setting ICSP port number to
New ICSP port number set, reboot the master for the change
to take affect.
SET ICSP TCP TIMEOUT Sets the timeout period for ICSP and i!-WebControl TCP connections.
Note: The new timeout value is immediately (no reboot required).
Example:
>SET ICSP TCP TIMEOUT
This will set the timeout for TCP connections for both
ICSP and i!-WebControl.When no communication has been
detected for the specified number of seconds, the socket
connection is closed.ICSP and i!-WebControl have built-in
timeouts and reducing the TCP timeout below these will
cause undesirable results. The default value is 45
seconds.
The current ICSP TCP timeout is 45 seconds
Enter new timeout (in seconds):
Once you enter a value and press the ENTER key, you get the follow-
ing message:
New timeout value set (in affect immediately).
SET IP <D:P:S> Sets the IP configuration of a specified device.
Enter a Host Name, Type (DHCP or Fixed), IP Address, Subnet Mask,
and Gateway IP Address.
Note: For NetLinx Central Controllers, the "Host Name" can only
consist of alphanumeric characters.
Enter Y (yes) to approve/store the information into the Master.
Enter N (no) to cancel the operation.
Note: The Device must be rebooted to enable new settings.
Example:
>SET IP [0:1:0]
--- Enter New Values or just hit Enter to keep current settings ---
Enter Host Name: MLK_INSTRUCTOR
Enter IP type. Type D for DHCP or S for Static IP and then Enter:
DHCP
Enter Gateway IP: 192.168.21.2
You have entered: Host Name MLK_INSTRUCTOR
Type DHCP
Gateway IP 192.168.21.2
Is this correct? Type Y or N and Enter -> y
Settings written. Device must be rebooted to enable new settings.