APC AP9608 Network Card User Manual


 
18
If the UPS is powered off during a status request, Call-
UPS II responds
with the message:
UPS Powered OFF
In addition to providing general status information, the UPS Status and
Diagnostics screen serves as a menu for obtaining more detailed informa-
tion on the Symmetra frames and external frames.
To go to the Main Frame screen, type 1 and press
ENTER. The following
display will appear.
The Main Frame screen is a map of the Symmetra array. The left column
displays the five levels of power module slots (
L1 to L5). The box at the
top of the right column displays the status of the Redundant Intelligence
Module (
RIM) on the first line and the status of the Intelligence Module
(
IM) on the second line. The remainder of the right column displays the
four levels of batteries. The power module and battery boxes display the
status of the corresponding power module or battery on the second line.
The Main Frame screen also serves as a menu for more detailed informa-
tion on each of the power modules and the intelligence modules. By typ-
ing
L1 and pressing ENTER, for example, you can view a screen that dis-
plays information regarding Power Module
L1. For information on the
Intelligence Module, type
IM and press ENTER, and so on. Included in
this information are hardware and firmware version numbers and the
Main Frame
+---------------+–--------------+
L1- | Power Module | None | -RIM
| No Module IIC | OK | -IM
+---------------+---------------+
L2- | Power Module | Battery |
|OK | OK |
+---------------+---------------+
L3- | Power Module | Battery |
|OK | OK |
+---------------+---------------+
L4- | Power Module | Battery |
|OK | OK |
+---------------+---------------+
L5- | Power Module | Battery |
| BAD | None |
+---------------+---------------+
<ENTER>=Refresh, <ESC>=Status Menu, ?=Help, or module
code for details>