APC AP9608 Network Card User Manual


 
25
With Symmetra Power Array
Call-UPS II connected to a Symmetra Power Array displays the following
UPS Characteristics menu:
------------------------------ UPS CHARACTERISTICS ---------------------------
UPS ID: UPS_IDEN
1- Output: 240 V
2- Output Freq Range: 60/.1 Hz
3- Output Voltage Reporting Base: Auto
4- If UPS fails and freq or voltage is out of range: Go to Bypass
-------------------------------------------------------------------------------
5- Low Battery Duration: 02 min.
6- Shutdown Delay: 020 sec.
7- Return Delay: 000 sec.
8- Return battery Capacity: 10 %
9- Scheduled Self Test: every 14 days
-------------------------------------------------------------------------------
10- Alarm if runtime is less than: 015 min.
11- Alarm if load is greater than: 05.0 kVA
12- Alarm if redundancy is less than: n+1 (0=never)
-------------------------------------------------------------------------------
13- Reset UPS to Default Settings
<ENTER> Display menu
<ESC> Return to Previous menu
>
To change a setting, type the number of the menu item and press ENTER.
The following screen displays when you enter “9.”
NOTE: Changes May Conflict with monitoring Software
Press <SPACE> To See Next Entry, <ENTER> To Accept
UPS Self Test> 14 Days
The following table gives a description of the settings on the UPS Char-
acteristics menu for Call-
UPS II connected to the Symmetra Power Array.