APC AP9608 Network Card User Manual


 
28
DATA/EVENT LOGGING
Item Default Description
Power
Events
ON
Call-UPS
II
will log power events, such as utility
line failure and battery exhausted, when enabled.
Enter 0 when prompted to disable, 1 to enable.
UPS Control ON
Call-UPS
II
will log control events, such as UPS
turned on and UPS in bypass, when enabled. Enter
0 to disable, 1 to enable.
UPS Faults ON
Call-UPS
II
will log UPS faults, such as UPS is
overloaded, and internal temperature too high,
when enabled. Enter 0 to disable, 1 to enable.
User
Activity
ON
Call-UPS
II
will log user activity, such as users
logging on and password changes, when enabled.
Enter 0 to disable, 1 to enable.
Measure-UPS OFF
Call-UPS
II
will log Measure-UPS alarms, e.g.,
high temperature, low temperature, and contact
closure, when enabled. Enter 0 to disable, 1 to
enable.
List Event
Groups
Displays a list of all reportable events, sorted into event
groups.
View Event
Log
Displays the event log. Call-UPS
II
pauses after each page of
log information.
Reset Event
Log
Clears the event log. Log information is kept in non-volatile
memory, so log items remain even when Call-UPS
II
is off.
Log UPS Data
to Screen
Queries the UPS for operating data at preset intervals (see
next item) and displays this information on the screen.
Call-UPS
II
reports date, time, current line voltage, mini-mum
line voltage, maximum line voltage, battery voltage, line
frequency, internal UPS temperature, and UPS load.
Log
Interval
Time interval at which Call-UPS
II
queries the UPS for log
data. The default is 1 minute. Set from 1 to 99 minutes
between queries, depending on how much data is needed.
Data Format
Choose one of two log data output formats. Use text, the
default, if the data will be used in word processing programs.
Use the comma delimited format for importing the data into
spreadsheets or databases.