APC NBRK0200 Power Supply User Manual


 
NetBotz Rack Monitor 200 Installation and Quick Configuration Manual10
How to Connect Sensors to Universal Sensor Ports
This procedure applies to the following sensors, which are supported by the Rack Monitor 200 and
connect to the universal sensor ports:
Temperature Sensor (AP9335T)
Temperature/Humidity Sensor (AP9335TH)
NetBotz 3.65-m (12-ft) Door Switch Sensor for APC Racks (NBES0303)
NetBotz 15.24-m (50-ft) Door Switch Sensor for Rooms or Third Party Racks (NBES0302)
NetBotz Dry Contact Cable (NBES0304)
For sensors that connect to A-Link ports (Temperature Sensors with Digital Display
[AP9520T] and Temperature/Humidity Sensors with Digital Display [AP9520TH]), see “How
to Cascade Devices to A-Link Ports” on page 12.
Caution: Plugging an incompatible sensor into a port can result in undefined behavior.
Connect APC and third-party dry contact sensors to the six universal sensor ports, labeled Sensors, on
the Rack Monitor 200.
Third-party dry contact sensors require the NetBotz Dry Contact Cable (NBES0304). To connect
a sensor to the cable, follow the instructions provided with the sensor and the instructions
provided with the cable.
The length of a sensor cable can be extended using RJ-45 female-to-female couplings and
standard CAT-5 cabling. See “System Specifications” on page 24 for maximum cable lengths.