Compaq UPS R3000 XR Personal Computer User Manual


 
3-10
Compaq UPS R3000 XR Maintenance and Service Guide
4.
Pull out the battery pack. Set aside the used battery pack for proper disposal. See
“Disposing of Used Batteries,” in this chapter.
Figure 3-8. Removing the battery pack
WARNING:
The UPS R3000 XR battery pack weighs 42 lb (19 kg). Prepare the area and
observe all materials handling procedures for removing the battery pack.
5.
Slide the new battery pack into the chassis.
6.
Replace the metal battery bracket and secure the two screws.
7.
Snap on the front bezel.
8.
Initiate a UPS self-test by pressing the TEST/ALARM RESET button.
Disposing of Used Batteries
The UPS uses sealed lead/acid batteries that must be disposed of in accordance with local
environmental regulations and laws.
If a local approved recycle/disposal site is not available, your replacement battery kit includes
the instructions and packaging required to return used batteries to an appropriate location for
disposal.
Pb
Do not dispose of used batteries with general office or household waste.
Return the used battery for proper disposal to:
!
Compaq, your authorized Compaq Partners, or their agents
!
A recycling center that meets all local environmental standards