Compaq UPS R3000 XR Personal Computer User Manual


 
3-16
Compaq UPS R3000 XR Maintenance and Service Guide
Replacing the UPS Unit
To replace the UPS:
1.
Power down the UPS. Follow the procedure in “Powering Down the UPS,” in this chapter.
2.
Turn all battery circuit breakers on the ERMs (one circuit breaker each) to the Off
position.
Figure 3-15. Switching the circuit breaker to the Off position
3.
Unplug the UPS power cable.
4.
Unplug connected devices and remove the retention clips that secure device cables to the
UPS.
5.
Unplug an attached ERM from the back of the UPS.
Figure 3-16. Unplugging the Extended Runtime Module