Cooper Bussmann BU-905U-L Network Router User Manual


 
18
www.cooperbussmann.com/BussmannWirelessResources
Cooper Bussmann BU-905U-L Wireless I/O Installation Manual
Status Outputs
The unit contains the following status outputs:
System OK;
Setpoint Output; and
Communications Failure.
Status outputs are FET output to common rated at 30Vdc 500mA.
Connect the output circuit to the appropriate Status Output terminal. Each status output circuit is associated with an LED indicator that lights lit
when the digital output is active.
The following table details the status output behavior:
Status Output
LED LED Status Description
System OK active (both modules) OK Green No fault detected
System OK inactive OK Red • Internal fault detected.
• Supply voltage Low
• Analog Loop supply overloaded
Setpoint Output (BU-905U-L-T) SP Green Local setpoint attached to 4-20mA analog input.
Communications Failure (BU-905U-L-R) CF Red Watchdog alarms active on digital outputs or analog outputs.
Analog Input
The BU-905U-L-T module provides one 0-20mA DC analog input for connecting to instrument transducers (e.g. level, moisture, pressure
transducers, etc.).
Note: The BU-905U-L-T module inputs measure down to 0mA and can also be used for zero based signals (e.g., 0-10mA).
The analog input has a positive and negative terminal and can be placed at any point in the current loop, providing neither input rises above the
24 volt Analog Loop Supply level.
Each input has a loop resistance of less than 250 ohms and zener diode protection is provided against over-voltage and reverse voltage.
Note: You may require additional protection in high voltage or noisy environments or for long wiring runs.
A 24Vdc loop supply is available on the BU-905U-L-T module for powering the analog transducer loops. In this situation, connect the:
Analog loop - between an Analog Input (-) terminal and Ground.
Positive terminal – i.e., Analog Input (+) to the +24V Analog Loop Supply.
Externally powered loops may be connected by connecting the input between "Analog Input (+)" and “Analog Input (-)” Common mode voltage
may be -0.5V to 27V.
3A1580Rev1.6