Emerson 00825-0100-4075 Network Card User Manual


 
Quick Installation Guide
00825-0100-4075, Rev BA
February 2010
Smart Wireless THUM Adapter
22
Hazardous Locations Certificates
North American Certifications
Factory Mutual (FM) Approvals
I5 FM Intrinsically Safe and Non-incendive
Intrinsically Safe for Class I/II/III, Division 1, Groups A, B, C, D, E, F, and G.
Zone Marking: Class I, Zone 0, AEx ia llC
Temperature Codes T4 (-50 °C T
amb
70 °C)
Non-incendive for Class I, Division 2, Groups A, B, C, and D.
Intrinsically safe and non-incendive when installed according to Rosemount Drawing
00775-0010.
Enclosure Type 4X/IP66
CSA - Canadian Standards Association
I6 CSA Intrinsically Safe
Intrinsically Safe for Class I, Division 1, Groups A, B, C, and D.
T3C (-50 °C T
amb
70 °C)
Intrinsically safe when installed according to Rosemount Drawing 00775-0012.
Suitable for Class I, Division 2, Groups A, B, C, and D.
Enclosure Type 4X/IP66
European Certifications
I1 ATEX Intrinsic Safety
Certificate No.: Baseefa09ATEX0125X II 1G
Ex ia IIC T4 (-50 °C T
amb
70 °C)
IP66
1180
Special conditions for safe use (X)
The surface resistivity of the antenna is greater than one gigaohm. To avoid electrostatic
charge build-up, it must not be rubbed or cleaned with solvents or a dry cloth.
The enclosure is made of aluminium alloy and given a protective polyurethane paint
finish; however, care should be taken to protect it from impact or abrasion if located in a
zone 0.
N1 ATEX Type n
Certificate No.: Baseefa09ATEX0131 II 3 G
Ex nA IIC T4 (-50 °C T
amb
70 °C)
Ui = 45 Vdc MAX
IP66
1180
Table 2. Input Parameters
Loop Power
Ui = 30V
Ii = 200 mA
Pi = 1.0 W
Ci = 0
Li = 0
4075_QIG_Rev_BA.fm Page 22 Friday, February 19, 2010 11:08 AM