Emerson 00825-0100-4075 Network Card User Manual


 
Quick Installation Guide
00825-0100-4075, Rev BA
February 2010
Smart Wireless THUM Adapter
23
IECEx Certifications
I7 IECEx Intrinsic Safety
Certificate No.: IECEx BAS 09.0050X
Ex ia IIC T4 (-50 °C T
amb
70°C)
IP66
Special conditions for safe use (X)
The surface resistivity of the antenna is greater than one gigaohm. To avoid electrostatic
charge build-up, it must not be rubbed or cleaned with solvents or a dry cloth.
The enclosure is made of aluminium alloy and given a protective polyurethane paint
finish; however, care should be taken to protect it from impact or abrasion if located in a
zone 0.
N7 IECEx Type n
Certificate No.: IECEx BAS 09.0058
Ex nA IIC T4 (-50 °C T
amb
70°C)
Ui = 45 Vdc MAX
IP66
Table 3. Input Parameters
Loop Power
Ui = 30V
Ii = 200 mA
Pi = 1.0 W
Ci = 0
Li = 0