Emerson 5500 SERIES Server User Manual


 
Setup Program – Serial Connection Thin Web Server
4-4
Alarms - Email Address
Alarms - ATS Power Manager Setting
Alarms - Engine PM Details
6. Click the Email Address lower tab. Then enter the e-mail
addresses (up to 5) of the persons whom you want
notified of the selected alarms. Double check each e-mail
address displayed in the five text boxes to verify that it
has been typed correctly.
Note: Make sure outgoing mailserver is configured
properly and working. This functionality can be
tested with third party e-mail testing programs.
7. Click the ATS Power Manager Setting lower tab. The
Network 1 Power Managers (addresses) are displayed
first. For each Power Manager (PM) address click the
drop-down arrow and select the appropriate icon number
associated with the PM. If a Power Manager:
- is with an ATS, select icon 1.
- is with a circuit breaker, select icon 3 or 4.
- is not
associated with an ATS or a CB, select icon 2.
Then click View Network 2 Settings and select icons for
those PMs.
8. Click the Engine PM Details lower tab. Network 1 & 2
Engine Power Manager (addresses 33-36) are displayed.
Enter a Description and Location for each PM. Then
select the appropriate icon associated with each PM.
Select if device is associated with CCM, EGCP, or both.
9. Click the Engine Power Manager Setting lower tab.
Select the check boxes Status Inputs and/or Discrete
Outputs that you want included in alarms monitoring.
continued on the next page
Ö
Alarms - Engine Power Manager Setting