Emerson 5500 SERIES Server User Manual


 
Symptom
Possible
Problem
Possible
Cause
Action Prevention
5. TWS booted but no client
or browser can not connect
to it.
TWS is not
connected to
LAN.
– LAN cable is damaged
or not properly plugged
into the TWS.
– LAN cable is not
connected to LAN1 port
of the TWS.
– No TCP/IP IP, subnet,
gateway assigned to the
TWS.
– The hub’s uplink mode
must be enabled at all
times.
– Make sure the connection between the
TWS and the LAN is done properly and
secured.
– Use LAN1 port of the TWS for LAN
connection. LAN2 port must never be used.
– If suspicious of the LAN cable RJ45, use a
cross-over cable to connetct the TWS with
the client station.
– Make sure the TSSP was used to configure
the TWS TCP/IP settings. After any
configuration download by the TSSP, make
sure to re-download the configuration from
the TWS to make sure that the
configuration data was uploaded properly
to the TWS.
– Make sure that both the subnet and gateway
addresses of the TWS and the client
stations are the same.
– Strictly follow the connection
diagram discussed in this
Installation Manual when
connecting the TWS.
– Make sure you have run the TSSP
first to configure the TWS before
attempting to connect to it through
a client station.
– If the TWS is installed in an
existing LAN, make sure you only
assigned IP, subnet, and gatewary
addresses to the TWS given to you
by the LAN administrator.
– Make sure the client station is also
connected to the TWS.
– You can use the ping application
which is a resident DOS utility in
your client station to verify
connection to the TWS.
6. TWS booted but found no
serial ASCO devices.
Devices
were not
properly
connected to
the TWS.
– Device incorrect wiring.
– 72As not functioning.
– Break in the line
somewhere in the daisy-
chained connection.
– Damaged TWS
connectors.
– Disabled COM4
communication.
– Devices are not
configured properly –
protocol & baud rate.
– Damaged TWS COM3
or COM4 RS485 ports.
– Check the connection of the daisy-chained
network of device to the TWS. Serial
daisy-chained network must be connected
only to COM3 & activated COM4 of the
TWS.
– Check connection between 72As.
– Check TTL connections of devices to the
72As.
– Install a repeater for daisy-chain
interconnect exceeding 4000 feet.
– Install terminating resistor at the last 72A
node of the daisy-chain network to avoid
noise and signal loss.
– Make sure to call for ASI for assistance
when symptoms become apparent and
conditions worsen.
– Strictly follow the connection
diagram discussed in this
Installation Manual when
connecting the TWS.
– Make sure all the ASCO devices
are configured properly.
– Follow recommeded remedies to
avoid noise and signal loss on
networks exceeding required
distance or installed in extreme
environments.