4.1 Agency and Certifications
Safety Standard: IEC/EN/AS 62040-1-1 incorporating applicable portions of IEC/EN/UL/AS 60950-1
Certification: CE and UL 60950-1:2003, First Edition CSA C22.2 No. 60950-1-03 1st Ed.
Electromagnetic Compatibility Standard: IEC/EN/AS 62040-2 incorporating applicable portions
of emission and immunity standards as detailed in Tables 20 and 21 below.
Table 20 Electromagnetic interference (EMI)—emission limits
Standard IEC/EN/AS Class
Harmonic Current 61000-3-2 -
Voltage Fluctuations & Flicker 61000-3-3 -
Conducted RFI CISPR 22 A
Radiated RFI CISPR 22 A
Table 21 Electromagnetic susceptibility (EMS)—immunity levels
Standard
IEC/EN/AS Requirement Level Criterion
Electrostatic Discharge
61000-4-2
6 kV contact, 8 kV air 3 B
Radiated Electric Fields
61000-4-3
10 V/m 3 A
Fast Electrical Transients
61000-4-4
2 kV / 5 kHz (Power and Signal ports) 3 B
Surges
61000-4-5
Power port
2kV (common mode)
1kV (differential mode)
Signal port
1kV
3B
Continuous Conducted Interfer.
61000-4-6
10V 3 A
Magnetic Field at Power Freq
61000-4-8
30A/m - B
Voltage Dips and Short
Interruptions
61000-4-11
70%Ut:
1ms, 3ms, 10ms A
30ms, 100ms, 300ms, 1000ms B
40%Ut:
1ms, 3ms A
10ms, 30ms, 100ms, 300ms, 1000ms B
0%Ut
1ms A
3ms, 10ms, 30ms, 100ms, 300ms, 1000ms B
Low Frequency Signals
61000-2-2 10V 140Hz-250Hz-360Hz
—A