Emerson Xtreme Density Network Card User Manual


 
Liebert XD Cooling Modules—Liebert XDO, Liebert XDV, Liebert XDH and Liebert XDCF
34
4.2.1 Optional Features—Liebert XDV
Refrigerant Pre-Charge—Liebert XDV units with the pre-charged refrigerant option will have
one-shot style fittings or removable couplings that contain pressurized refrigerant inside the Lie-
bert XDV. The fittings ease connection to Liebert XD Piping and filling with refrigerant.
External Mounting Brackets—The Liebert XDV can be suspended from the overhead building
structure. The external mounting brackets are ship-loose items.
Field-Installed Flexible Piping (for use with prefabricated piping assemblies)—Field-installed
flexible piping kits are available in lengths of 4, 6, 8 and 10 feet (1.2, 1.8, 2.4 and 3 meters). Con-
nection style to the unit end may be straight or 90 degrees. Connection to the prefabricated piping
assembly is with a threaded coupler. For information on acquiring the correct kit for your instal-
lation, refer to DPN000781_Rev1, available from Liebert by calling 1-800-LIEBERT and from
your local Emerson Network Power representative.
Condensate Detection—The Liebert XDV unit is available with factory-installed condensate
detection. The condensate detection has connection points (dry contacts) at the external rear of
the unit.
Figure 32 Liebert XDV dimensions
Rear
2-3/8"
(60.3mm)
2-5/8"
(66mm)
3/4"
(19mm)
3/4"
(19mm)
39-1/2"
(1003mm)
Depth, Top
Width
29-5/8"
(752mm)
18-5/8"
(473mm)
22-7/8"
(581mm)
14"
(355mm)
Unit Height
Piping
Height
Depth, Bottom
DPN000770, Page 2
Rev. 2
Schrader Valve
Supply (In)
Return (Out)