Emerson Xtreme Density Network Card User Manual


 
Specifications
71
Table 36 Liebert XDV8 specifications
Models
XDV8BK--*; XDV8DK--*
XDV8BKP-*; XDV8DKP-*
XDV8BK-E*; XDV8DK-E*
XDV8BKPE*;
XDV8DKPE*
XDV8BKR-*; XDV8BKRE*
XDV8DKR-*; XDV8DKRE*
XDV8BT--*; XDV8DT--*
XDV8BTP-*; XDV8DTP-*
XDV8BT-E*; XDV8DT-E*
XDV8BTPE*; XDV8DTPE*
XDV8BTR-*; XDV8BTRE*
XDV8DTR-*; XDV8DTRE*
XDV8BS--*; XDV8DS--*
XDV8BSP-*; XDV8DSP-*
XDV8BS-E*; XDV8DS-E*
XDV8BSPE*; XDV8DSPE*
XDV8BSR-*; XDV8BSRE*
XDV8DSR-*; XDV8DSRE*
60 Hz 60 Hz 50 Hz 50 Hz
Cooling Capacity
Nominal (98°F [37°C] EAT): 8.8kW / 2.5 Tons
Maximum (95°F [35°C] EAT): 8.8kW / 2.5 Tons
Nominal (98°F [37°C] EAT): 8kW/ 2.3 Tons
Maximum (103°F [39°C] EAT): 8.8kW/2.5Tons
Conditions
Capacity rating is @ 55ºF (13ºC) Entering Fluid Temperature and
50ºF (10ºC) or lower dew point, rear air inlet.
Electrical Requirements
Input 120V model: 1ph-60 Hz 230V model: 1ph-60 Hz 230V model: 1ph-50 Hz
Input power connections 2 power connections, each model
Full Load Amps 120V model: 2.0A 230V model: 1.0A
Power consumption,
nominal, watts
180 190 190 190
Dimensions, inches (mm)
Height – unit only 14 (355) not including pipe connections
Height – including pipe
connections
18-5/8 (473)
Width 22-7/8 (581)
Depth – Top 39-1/2 (1003)
Depth – Bottom 29-5/8 (752)
Weight, lb (kg)
Unit only 77 (35)
Shipping weight 125 (57)
Installed, with
refrigerant
79 (36)
Number of Fans 2222
Airflow, Nominal,
ft
3
/ min (m
3
/ hr)
1000 (1699) with rear inlet. Bottom inlet airflow may
be less, depending on restrictions inside cabinet
833 (1415) with rear inlet. Bottom inlet airflow
may be less, depending on restrictions inside
cabinet
Audible noise 78 dBa sound power 73 dBa sound power
Pipe Connections (without Liebert Flex Pipe)
Refrigerant Supply
from Liebert
XDP/Liebert XDC
1/2" OD Cu, (optional 1/2" threaded coupler flex piping)
Refrigerant Return
to Liebert XDP/Liebert
XDC
5/8" OD Cu, (optional 3/4" threaded coupler flex piping)
Serviceable Parts Fans and electrical components
Cabinet Exterior
Finish
Black, matte finish, heat-fused powder coat
Options
Condensate sensing
(factory-installed)
Dry contact outgoing signal
Pre-Charged R-134a Refrigerant, one-shot connections
Agency
Approvals CSA 60Hz CSA 50Hz CE 50Hz
* = Revision level of unit