Emerson Xtreme Density Network Card User Manual


 
Liebert XD Cooling Modules—Liebert XDO, Liebert XDV, Liebert XDH and Liebert XDCF
51
4.10 Liebert XDP Standard Features
Heat Exchanger—Brazed plate design with interwoven circuiting constructed of stainless steel
plates, copper brazed.
Pumps—Centrifugal type, end suction, internally cooled, canned rotor design.
Standard Control Processor—The standard control system is microprocessor-based with an exter-
nal LCD numerical display to allow observation of specified adjustable functions. Operating con-
ditions and status are indicated on the LCD panel, which is mounted either on the unit or on the
wall, depending on application details (see user manual, SL-16641). The control system also mon-
itors unit operation and activates an alarm when any of the specified factory preset conditions are
exceeded.
Cabinet and Frame—Custom powder painted steel panels. A hinged control access panel opens to
a second front panel, which is a protected enclosure for all high voltage components. Frame is con-
structed of 14 gauge heliarc welded tubular steel and painted using an auto-deposition coating
system.
Figure 50 Liebert XDP dimensions
Table 22 Liebert XDP dimensions
Model
50/60Hz
Dimensional Data inches (mm) Shipping Weight, lb (kg)
A B C D E Domestic Export
Liebert
XDP160
38 (965) 34 (864) 33-1/8 (841) 33 (838) 36 (914) 990 (449) 1067 (484)
* The dimension does not include the bezel of the disconnect switch.
Unit Dimensional Data
Floor Cutout Dimensions
E
D
A
Overall
C
Side Panel
B
Overall
DPN000767
Pg. 2, Rev. 6
D
Unit Base
E
Unit Base
78"
(1981mm)
11"
(279mm)
5
"
(
1
2
7
m
m
)
1" (25mm)
5-1/2"
(140mm)
The shaded area indicates
a recommended clearance
of 36" (914mm) for component
access.