Specifications
74
Table 41 Liebert XDH specifications
Models
XDH20DKP-0
XDH20DK--0
XDH20BKP-0
XDH20BK--0
XDH20DKPE0
XDH20DK-E0
XDH20BKPE0
XDH20BK-E0
(60Hz)
XDH32DKP-0
XDH32DK--0
XDH32BKP-0
XDH32BK--0
XDH32DKPE0
XDH32DK-E0
XDH32BKPE0
XDH32BK-E0
(60Hz)
XDH20DSP-0
XDH20DS--0
XDH20BSP-0
XDH20BS--0
XDH20DSPE0
XDH20DS-E0
XDH20BSPE0
XDH20BS-E0
(50/60Hz)
XDH32DSP-0
XDH32DS--0
XDH32BSP-0
XDH32BS--0
XDH32DSPE0
XDH32DS-E0
XDH32BSPE0
XDH32BS-E0
(50/60Hz)
Cooling Capacity
XDH20, 60Hz Nominal (98ºF [37°C] EAT): 22kW/6.3 Tons
XDH20, 60Hz Maximum(105ºF [40°C] EAT): 25.5kW/7.3 Tons
XDH20, 50Hz Nominal (98ºF [37°C] EAT): 19kW / 5.4 Tons
XDH20, 50Hz Maximum(116ºF [47°C] EAT): 25.5kW/7.3 Tons
XDH32, 60Hz Nominal (98ºF [37°C] EAT): 30kW/8.5 Tons
XDH32, 60Hz Maximum(105ºF [40°C] EAT): 34.5kW/7.3 Tons
XDH32, 50Hz Nominal (98ºF [37°C] EAT): 27kW / 7.7 Tons
XDH32, 50Hz Maximum(108ºF [42°C] EAT): 34.5kW/7.3 Tons
Conditions
Capacity rating is @ 55ºF (13ºC) Entering Fluid Temperature and 50ºF (10ºC) or lower dew
point
Electrical Requirements
Input 120V-1ph-60Hz
220-240V-1ph-50Hz, CE /
208-240V-1ph-60Hz, CSA
Input Power Connections
Two IEC320-C14 power inlets and two IEC
power cords with NEMA 5-15P connectors
Two IEC320-C14 power inlets and two IEC
power cords with IEC320-C14 receptacles
Full Load Amps 5 10 2.5 5
Power Consumption,
Nominal, Watts
600 1200 575 1150
Dimensions, inches (mm)
Height—Unit Only 78 (1981)
Height—Including
Pipe Connections
80 (2032)
Width 12 (305)
Depth 42 (1067)
Weight, lb (kg)
Unit Only 233 (106) 246 (112) 233 (106) 246 (112)
Shipping Weight 317 (144) 330 (150) 317 (144) 330 (150)
Number of Fans
6
Airflow, Nominal,
ft
3
/min (m
3
/hr)
2500 (4248) 4000 (6796) 2428 (4125) 3850 (6541)
Audible Noise,
Sound Power
81 dBa 86 dBa 81 dBa 86 dBa
Pipe Connections
Refrigerant Supply 1/2" OD, Cu (optional 1/2" threaded one-shot coupling on the unit)
Refrigerant Return 7/8" OD, Cu (optional 7/8" threaded one-shot coupling on the unit)
Serviceable Parts Fans and electrical components
Cabinet Exterior Finish Black, matte finish, heat-fused powder coat
Options
Condensate Sensing (factory-installed)
Dry contact outgoing signal (24VAC - 1A maximum)
One-shot style flex pipe connections
Uni-directional or bi-directional air diffusers
Agency
Approvals CSA 60Hz CE 50Hz, CSA 50/60Hz