Emerson Xtreme Density Network Card User Manual


 
Liebert XD Cooling Modules—Liebert XDO, Liebert XDV, Liebert XDH and Liebert XDCF
56
Figure 57 Liebert XDC piping locations
Table 25 Liebert XD Chiller piping connection sizes
Air Cooled Models Piping Outlet Connection Sizes, OD Cu, inches
50/60Hz A B C D E F G
Liebert XDC160 1-3/8 7/8 - - - 2-1/8 1-1/8
Install replaceable filter dryer
assembly in liquid supply line G
** To first cooling module
or bypass flow controller
Dimensions are
approximate and
subject to change
without notice.
G - Supply to Cooling Units
F - Return From Cooling Units
B - Liquid
Refrigerant Lines
* Allow 8" (204mm) of clearance for filter replacement
** To ensure all refrigerant flow is filtered, install the filter dryer assembly
between the discharge line of the XDC and the first bypass flow controller
or the first cooling module.
A - Hot Gas
Refrigerant Lines
* Orientation determined
by installer.
23"
(584.2mm)
6" (152mm)
47"
(1193.8mm)
44"
(1117.6mm)
DPN000768
Page 3, Rev. 6