FieldServer FS-8700-21 Computer Drive User Manual


 
FS-8700-21 LonWorks Manual Page 26 of 62
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com
LonMark Config file Example #1 Open Loop “Water Temperature” Sensor:
// Client Side Map Descriptors
Map_Descriptors
Map_Descriptor_Name
,Data_Array_Name
,Data_Array_Offset
,Lon_Function
,Function
,Node_Name
,SNVT_Index
,SNVT_Type
,Nv_Min_Value
,Nv_Max_Value
,Nv_Selfdoc_text
nvoTemp
,DA_FI_01
,0
,NVUOIMC
,Wrbc
,LON_1
,-
,SNVT_Temp_f
,-
,-
,“@0|1;WaterTemp”
NviTempMin
,-
,-
,CFG_NVUI
,Server
,LON_1
,-
,SNVT_Temp_f
,10
,-
,“&200\x8023”
NviTempMax
,-
,-
,CFG_NVUI
,Server
,LON_1
,-
,SNVT_Temp_f
,-
,300
,“&200\x8020”
LonMark Config file Example #2 “Water Heating Element” Actuator:
// Client Side Map Descriptors
Map_Descriptors
Map_Descriptor_Name
,Data_Array_Name
,Data_Array_Offset
,Lon_Function
,Function
,Node_Name
,SNVT_Index
,SNVT_Type
,Nv_Min_Value
,Nv_Max_Value
,Nv_Selfdoc_text
nvoTemp
,DA_FI_01
,0
,NVUOIMC
,Wrbc
,LON_1
,-
,SNVT_Temp_f
,-
,-
,“@0|1;WaterTemp”
NviTempMin
,-
,-
,CFG_NVUI
,Server
,LON_1
,-
,SNVT_Temp_f
,10
,-
,“&200\x8023”
NviTempMax
,-
,-
,CFG_NVUI
,Server
,LON_1
,-
,SNVT_Temp_f
,-
,300
,“&200\x8020”
The Node Self-
Documentation String
defines one LonMark
object of type 1 Open
Loop Sensor.
These two configuration network variables will be linked to the first
Map Descriptor declared. The NV_Min_Value and NV_Max_Value fields
define the defaults for these CP’s. These defaults are loaded by the
FieldServer after a restart only when re-commissioning is required.
The object index is 0 and
this Map Descriptor
defines the 1
st
Network
Variable of the object.
The Node Self-
Documentation String
defines one LonMark
object of type 3 Open
Loop Actuator.
These two configuration network variables will be
linked to the first Map Descriptor declared. The
NV_Min_Value and NV_Max_Value fields define the
defaults for these CP’s. These defaults are loaded by
the FieldServer after a restart only when re-
commissioning is required.
The object index is 0 and
this Map Descriptor
defines the 1
st
Network
Variable of the object.