FS-8700-21 LonWorks Manual Page 52 of 62
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com
SNVT_pump_sensor
Data Length
13
Suggested Data Array Formats
Float
Data Item 1
pump_sn_rot_speed
Measurement
Units
Values Range
Invalid Value
Frequency
Hertz
0 .. 6,553.4
N/A
Data Item 2
pump_sn_body_temp
Measurement
Units
Values Range
Invalid Value
Body temperature
Degrees celcius
-274.0 .. 6,279.4
N/A
Data Item 3
pump_sn_mot_ext_temp
Measurement
Units
Values Range
Invalid Value
Motor external
temperature
Degrees celcius
-274.0 .. 6,279.4
N/A
Data Item 4
pump_sn_mot_int_temp
Measurement
Units
Values Range
Invalid Value
Motor internal
temperature
Degrees celcius
-274.0 .. 6,279.4
N/A
Data Item 5
pump_sn_mot_overload
Measurement
Units
Values Range
Invalid Value
Boolean
Bit
0, 1
255 (0xFF)(BOOL_NUL)
Data Item 6
pump_sn_oil_low
Measurement
Units
Values Range
Invalid Value
Boolean
Bit
0, 1
255 (0xFF)(BOOL_NUL)
Data Item 7
pump_sn_ph_imbal
Measurement
Units
Values Range
Invalid Value
Boolean
Bit
0, 1
255 (0xFF)(BOOL_NUL)
Data Item 8
pump_sn_curr_use
Measurement
Units
Values Range
Invalid Value
Electric current usage
Ampere
-3,276.8 ..
3,276.6
N/A
Data Item 9
pump_sn_pwr_usage
Measurement
Units
Values Range
Invalid Value
Power usage
Kilowatts
0 .. 6,553.4
N/A
Data Item 10
pump_sn_temp_ctrl
Measurement
Units
Values Range
Invalid Value
unit_temp_t
N/A
0 .. 3
255 (0xFF)(TEMP_NUL)
Data Item 11
pump_sn_em_brake_act
Measurement
Units
Values Range
Invalid Value
Boolean
Bit
0, 1
255 (0xFF)(BOOL_NUL)
Data Item 12
pump_sn_fric_brk_act
Measurement
Units
Values Range
Invalid Value
Boolean
Bit
0, 1
255 (0xFF)(BOOL_NUL)
Data Item 13
pump_sn_gas_brk_act
Measurement
Units
Values Range
Invalid Value
Boolean
Bit
0, 1
255 (0xFF)(BOOL_NUL)