FS-8700-21 LonWorks Manual Page 5 of 62
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com
2.3 Clients/Servers
The FieldServer functions as a Client when polling or sending updates on the LonWorks network and as a Server when being
polled or receiving updates. The FieldServer can be bound to a maximum number of 15 LonWorks Nodes. The FieldServer
recommended point limit is 1000 points for the FS-B2011 Series and 4096 points for the FS-B30 and FS-B4011.
2.4 Explicit/Implicit
Clients can address Servers using explicit or implicit addressing. Clients using explicit addressing obtain their data transfer
parameters directly from the FieldServer configuration file. Implicit addressing is used when a Network Management Tool
such as LonMaker® is used to connect a FieldServer to other LonWorks Nodes - the FieldServer is assigned its data transfer
(binding) parameters by the Network Management Tool.
2.5 XIF Files
At start-up the FieldServer creates an external interface file (XIF) called fserver.xif based on the configuration file. The
FieldServer differs from most other LonWorks drivers in that it is configurable and therefore its XIF is not fixed for all
applications. The list of points available to the network will vary depending on the other networks connected to the
FieldServer, and the requirements of the particular application. The recommended procedure for obtaining the XIF file for
the FieldServer is to upload it. Refer to Appendix A.4 for details.
2.6 Device Resource Files
The STANDARD device resource file covers FieldServer data type support. All Standard Network Variable Types (SNVTs) in
this file are available to the user. These SNVTs are listed in Section 5.1.3. Please note that due to the sophisticated nature of
LonWorks variables, it may not always be possible to typecast the full information supplied in a LonWorks variable to a simple
Data Type contained in another protocol. The FieldServer supports Move and Logic functions which would allow the
LonWorks variable to be split up and passed to separate simple data types, thus preventing information loss. The FieldServer
supports the sending and receiving of User-defined Network Variable Types (UNVTs) on the LonWorks Network. An UNVT is
simply implemented as an array of bytes of user-defined length.
2.7 NV Aliases
The FieldServer currently supports a default of 63 network variable aliases to avoid network variable connection constraints.
This number may be increased to a maximum of 4096.
2.8 Configuration Properties
Configuration Properties (CP’s) characterize the behavior of a device in the system. Network installation tools realize this
attribute and provide database storage to support maintenance operations. If a device fails and needs to be replaced, the
configuration property data stored in the database is downloaded into the replacement device to restore the behavior of the
replaced device in the system. Configuration properties are implemented on the FieldServer through configuration network
variables. User-defined configuration property types are not supported. Appendix A.5 provides a list of standard
configuration property types that are supported.
The information that follows describes how to expand upon the factory defaults provided in the configuration files included
with the FieldServer.