FS-8700-21 LonWorks Manual Page 31 of 62
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com
Appendix B.2. Neuron Systems
Newron Systems may produce the following Error message “bindings lost after power-cycle” The solution to this is
to place the FieldServer in the Configured state which will cause the bindings to be committed to the Neuron and
they will remain after a power cycle.
Procedure:
1) Make the bindings in NL220
2) Place devices in ONLINE mode or state.
3) Refer to the following Screencap for assistance in placing the FieldServer in the Configured state.
Appendix B.3. Honeywell Care
This system uses unacknowledged service as default. This protocol driver requires acknowledged service to
operate correctly.
Appendix B.4. Tridium JACE
This system uses unacknowledged service as default. This protocol driver requires acknowledged service to
operate correctly.
Note that Tridium calls Acknowledged service “critical bindings”.