SNVT_pumpset_mn
Data Length
14
Suggested Data Array Formats
Float
Data Item 1
pset_sn_dil_flow
Measurement
Units
Values Range
Invalid Value
Total Dilution Flow
Volume
Milliliters per second
0 .. 65,534
N/A
Data Item 2
pset_sn_exh_temp
Measurement
Units
Values Range
Invalid Value
Exhaust Temperature
Degrees Celcius
-274.0 .. 6,279.4
N/A
Data Item 3
pset_sn_exh_press
Measurement
Units
Values Range
Invalid Value
Exhaust Pressure
Kilo-pascals
-3,276.8 ..
3,276.6
N/A
Data Item 4
pset_sn_seal_press
Measurement
Units
Values Range
Invalid Value
Shaft seal purge
pressure
Kilo-pascals
-3,276.8 ..
3,276.6
N/A
Data Item 5
pset_sn_inlet_vacuum
Measurement
Units
Values Range
Invalid Value
Inlet vacuum pressure
Kilo-pascals
-3.40282E38 ..
3.40282E38
N/A
Data Item 6
pset_sn_supply_volts
Measurement
Units
Values Range
Invalid Value
Supply voltage
Volts
-3,276.8 ..
3,276.6
N/A
Data Item 7
pset_sn_cool_flow
Measurement
Units
Values Range
Invalid Value
Total coolant flow
Milliliters per second
0 .. 65,534
N/A
Data Item 8
pset_sn_cool_fl_low
Measurement
Units
Values Range
Invalid Value
Boolean
Bit
0, 1
255 (0xFF)(BOOL_NUL)
Data Item 9
pset_sn_dil_active
Measurement
Units
Values Range
Invalid Value
Boolean
Bit
0, 1
255 (0xFF)(BOOL_NUL)
Data Item 10
pset_sn_bal_dil_act
Measurement
Units
Values Range
Invalid Value
Boolean
Bit
0, 1
255 (0xFF)(BOOL_NUL)
Data Item 11
pset_sn_inl_p_dil_act
Measurement
Units
Values Range
Invalid Value
Boolean
Bit
0, 1
255 (0xFF)(BOOL_NUL)
Data Item 12
pset_sn_exh_dil_act
Measurement
Units
Values Range
Invalid Value
Boolean
Bit
0, 1
255 (0xFF)(BOOL_NUL)
Data Item 13
pset_sn_dil_fl_oor
Measurement
Units
Values Range
Invalid Value
Boolean
Bit
0, 1
255 (0xFF)(BOOL_NUL)
Data Item 14
pset_sn_pwr_sup_on
Measurement
Units
Values Range
Invalid Value
Boolean
Bit
0, 1
255 (0xFF)(BOOL_NUL)
SNVT_pwr_fact
Data Length
1
Suggested Data Array Formats
Float
Data Item 1
Measurement
Units
Values Range
Invalid Value
Power Factor
Multiplier
-1.00000 ..
1.00000
N/A