FS-8700-21 LonWorks Manual Page 58 of 62
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com
SNVT_state_64
Data Length
4
Suggested Data Array Formats
Packed_Bit, Uint16, Float
Data Item 1
state_64_word0
Measurement
Units
Values Range
Invalid Value
Boolean
Bit
0, 1 per bit ( 16
bits in word )
N/A
Data Item 2
state_64_word1
Measurement
Units
Values Range
Invalid Value
Boolean
Bit
0, 1 per bit ( 16
bits in word )
N/A
Data Item 3
state_64_word2
Measurement
Units
Values Range
Invalid Value
Boolean
Bit
0, 1 per bit ( 16
bits in word )
N/A
Data Item 4
state_64_word3
Measurement
Units
Values Range
Invalid Value
Boolean
Bit
0, 1 per bit ( 16
bits in word )
N/A
SNVT_str_asc
Data Length
31
Suggested Data Array Formats
Byte, Uint16, Float
Data Item 1 - 31
ascii00, ascii01, .. ascii30
Measurement
Units
Values Range
Invalid Value
Character String
N/A
0 .. 255
N/A
SNVT_str_int
Data Length
16
Suggested Data Array Formats
Uint16, Float
Data Item 1
char_set
Measurement
Units
Values Range
Invalid Value
Locale Code
N/A
0 .. 255
N/A
Data Item 2 - 16
wide_char00, ..
wide_char14
Measurement
Units
Values Range
Invalid Value
Wide-character string
with NULL terminator
N/A
0 .. 65,535
N/A
SNVT_scene
Data Length
2
Suggested Data Array Formats
Float
Data Item 1
Value
Measurement
Units
Values Range
Invalid Value
Value
Percentage of full scale
0 .. 100.0
N/A
Data Item 2
State
Measurement
Units
Values Range
Invalid Value
State
N/A
0 .. 1
-1
SNVT_telcom
Data Length
1
Suggested Data Array Formats
Byte, Uint16, Float
Data Item 1
Measurement
Units
Values Range
Invalid Value
telcom_states_t
N/A
0 .. 20
255 (0xFF)(TEL_NUL)
SNVT_temp
Data Length
1
Suggested Data Array Formats
Float
Data Item 1
Measurement
Units
Values Range
Invalid Value
Temperature
Degrees Celsius
-274.0 .. 6,279.5
N/A
SNVT_temp_diff_p
Data Length
1
Suggested Data Array Formats
Float
Data Item 1
Measurement
Units
Values Range
Invalid Value
Temperature
difference
Degrees Celcius
-327.68 .. 327.66
Raw: 32,767 (0x7FFF)
Type: 655.34