GarrettCom 6K32TRC Switch User Manual


 
Magnum 6K32T & 6K32TRC Managed Switch Installation and User Guide 05/07)
36
www GarrettCom com
..
There are three options of brackets available to mount in the standard 19”
frame, 23” frame, or ETSI (21”) frame. The 19” brackets are included with each unit, the
other two may be purchased as separate options.
With each bracket type, there are three different mounting options as shown in Fig. 3.3.2.
The case of the Magnum 6K32T has mounting holes prepared for each of the mounting
arrangements. Users may choose the mounting arrangement most suitable for their
installation.
3.4 Powering the Magnum 6K32T & 6K32TRC Managed Switch
The Magnum 6K32T & 6K32TRC Switches incorporate an internal universal
power supply and have a recessed male IEC connector for the AC power cord at the left-
rear. A manual power ON-OFF switch is adjacent. A six-foot 115 VAC 60 Hz standard
power cord is supplied with each unit shipped within the United States and Canada.
The auto-ranging power supply supports installation environments where the
AC voltage is from 90 to 260 volts with a power input frequency between 47 and 63 Hz.
The 32-port units will consume over 30 watts of power typically. When connecting the
Ethernet cabling, there is no need to power down the unit. Individual segments can be
connected or disconnected without concern for AC power-related problems or damage to
the unit.
Power supply options are available to suit the 6K32T & 6K32TRC Switches to
special high-availability communications and/or heavy industrial-grade applications,
including:
* -48VDC, 24VDC and 125VDC with single DC input,
* -48VDC, 24VDC and 125VDC with dual-source DC input,
See the Appendices of this manual for more details. Use an RFQ for other variations.
3.4.1 Alarm Contacts for monitoring internal power, and Software Traps
The Alarm Contacts feature, optional on Magnum 6K32T & 6K32TRC’s,
provides two Form C Normally Closed (NC) contacts to which the user can attach two
sets of status monitoring wires at the green terminal block. When this option is present,
the terminal block for Alarm Contacts is part of the Power Input panel in the Magnum
6K32T & 6K32TRC case. The AC or DC power input connection is in the same panel. A
manual On-Off Switch for power to the unit is not available on 6K32T & 6K32TRC units
with the Alarm Contacts option, as these two features occupy the same space in the case.
The first NC Alarm Contact (top position) is a “Software Alarm”, operated
by user settings in the MNS-6K software. The user can disable the Software Alarm
feature with a software configuration command if desired. When the Software Alarm is
enabled, the Form C Normally Closed (NC) contact is held close during normal software
operation. A user-defined software malfunction, such as an SNMP Trap or a Software