GE 225 Power Supply User Manual


 
g
GE
OPM_SGS_ISG_M22_M30_0US_V011.doc 15/38 Installation Guide
SG Series
225 & 300 kVA
3.5 VENTILATION AND COOLING
Fig. 3.5-1 Installation on plain floor Fig. 3.5-2 Installation on raised floor
The heat produced by the UPS is transferred to the environment by its ventilation.
Air inlets for UPS ventilation are located on the front of the UPS, while air outlets are on top
of the cabinet.
A suitable ventilation or cooling system must be installed to extract the heat from the UPS
room.
Do not put anything on the top of the cabinet.
Air filtration systems could be required when the UPS operates in a dirty environment.
Contact your
Dealer
or the nearest
Service Center
for appropriate solutions.
In order to prevent overheating of the UPS, the available air intake flow rate must exceed the
total air exhaust flow rate requirement of the UPS system.
The below table indicates the heat dissipation at full Load at PF = 0.8 lag. and charged
Battery
, up to 3,280 ft (1,000 m) altitude, for cooling air 77°F (25°C) to 86°F (30°C).
Losses Cooling air flow
UPS rating
BTU / hr kW CFM m
3
/ h
SG Series 225 kVA
50,512 14.80 2,541 4,317
SG Series 300 kVA
64,164 18.80 3,228 5,484