Lantronix 4092A IRIG-B Switch User Manual


 
14 3: Monitoring the 4092A
3.2.2 Checking Model Number and Software Version
Both commands are case sensitive. You do not need to type a carriage return or line feed.
To check the TSC model number:
Type: I
The system returns I4092A-00\r\n, where the 00 is the hardware version.
To check the software version
Type: V
The system returns Vxx\r\n where xx is the software version.
Example: V00.
S
Status command
S02000,00000
4092A set to autoswitch with active input set to B. Input A latched fault cleared.
A
Make channel A active
command
ALARM10000
Alarm output shows change in status. 4092A set to A with active input set to A.
S
Status command
S10000,12000
4092A set to A with active input set to A. Current status should match last alarm
output (ALARM10000). No latched alarms. Changed status (remote control bit
changed from B to A and active input changed from B to A).
S
Status command
S10000,00000
4092A set to A with active input set to A. No latched alarms. Changed status bits
cleared upon status request.
C
Autoswitch command
ALARM00000
Alarm output shows change in status. 4092A set to autoswitch with active input set
to A.
S
Status command
S00000,10000
4092A set to autoswitch with active input set to A. Current status should match last
alarm output (ALARM10000). No latched alarms. Changed status (remote control
bit changed from A to autoswitch).
S
Status command
S00000,00000
4092A set to autoswitch with active input set to A. No latched alarms. Changed
status bit cleared upon status request.
Table 2: Example Telnet session (Continued)
Command sent 4092A response