Unpacking the UPS and Site Preparation
7
2.4 Environmental Conditions
Install the Liebert
®
GXT3
™
indoors in a controlled environment where it cannot be accidentally
turned off. Place it on a level, even surface in an area with unrestricted airflow around the unit. The
installation location must be free of water, flammable liquids, gases, corrosives and other conductive
contaminants. Maintain a minimum clearance of 100mm (4 inches) in the front and rear of the UPS.
Maintain an ambient temperature range of 0 to 40°C (32 -104°F).
See 8.0 - Specifications for acceptable environmental conditions.
2.5 Access to Area
The area where the Liebert GXT3-10000T220 is to be placed must have sufficient space for
installation procedures and for routine maintenance. The UPS is narrow enough to pass through
standard doorways.
2.6 Floor Loading
Ensure that the floor where the UPS will be installed will support the unit’s weight (see Table 9 for
the unit’s weight).
2.7 Inventory List
• CD containing:
• Liebert MultiLink
®
shutdown software
•Configuration Software
• User Manual
• Terminal Block Communication terminals
• Floor-mount brackets
• Warnings, safety instructions booklet and WEEE recycling sheet (ISO 14001 compliance)
•USB cable
• Hardwire terminal block cover plate and mounting screws
• Single input bypass jumper
• Battery cabinets contain one DC power cable
NOTE
UPS operation in sustained temperatures outside the range of 15-25°C (59°-77°F) will reduce
battery life.