Specifications
26
Table 10 Battery cabinet specifications
Model Number
GXT3-240TBATTCE
Dimensions, W x D x H, in. (mm)
Unit 31.5 x 11.81 x 26.57 (800 x 300 x 675)
Shipping 41.8 x 16.7 x 34 (1062 x 426 x 866)
Weight, lb (kg)
Unit 243 (110)
Shipping 309 (140)
Internal Battery Parameters
Type Valve-regulated, non-spillable, lead acid
Quantity x V 2 x 20 x 12V
Battery Manufacturer, Part # CSB HR1234R or Panasonic UP-RW1245
Temperature Limits, Batteries Only,
°F (°C)
32 to 104 (0 to 40)
Backup Time See Table 11
Environmental
Operating Temp, °F (°C) 32 to 80 (0 to 27)
Storage Temp 5 to 104 (-15 to 40)
Transportation Temp, °F (°C) 5 to 122 (-15 to 50)
Relative Humidity 0-95% non-condensing
Operating Elevation Up to 3281 ft (1000m) at 80°F (27°C) without derating
Agency
Safety UL 1778, c-UL Listed
Transportation ISTA Procedure 1B
Table 11 Typical battery run times for the Liebert
®
GXT3-10000T230
™
Number of Batteries,
Battery Cabinets
Load %
10% 20% 30% 40% 50% 60% 70% 80% 90% 100%
Internal Battery 81 39 22 15 11 8 6 5 4 3
Internal Battery + 1
External Battery Cabinet
190 127 81 60 46 39 32 26 22 18
Internal Battery + 2
External Battery Cabinets
316 162 136 106 82 69 52 48 44 39
Approximate discharge times are at 77°F (25°C) with a 100% resistive load.