Liebert GXT3-10000T220 Power Supply User Manual


 
Specifications
25
8.0 SPECIFICATIONS
Table 9 Liebert
®
GXT3
specifications
Model Rating, VA (W)
10,000 (9000)
Dimensions, in. (mm)
Unit, W x D x H 31.5 x 11.81 x 26.57 (800 x 300 x 675)
Shipping, W x D x H 41.8 x 16.7 x 34 (1062 x 426 x 866)
Weight, lb (kg)
Unit 308 (140)
Shipping 428 (194)
Input AC Parameters
Nominal Operating Frequency 50 or 60Hz (Factory Default = 60)
Factory Default VAC 120/208 at 120 degrees
User-Configurable VAC 120 / 208 / 220 / 240
Operating Voltage Range
Without Battery Operation
100 - 185 ±5VAC
Maximum Allowable VAC 280
Input Frequency
Without Battery Operation
40 - 70Hz
Input Power Connection BYP, L1, L2, GND
Output AC Parameters
Factory Default, VAC 208
Output Connections
Hardwire Terminal Block
Output: (GEC, X1, X2, X3, X4, GND) Bypass: L1, L2, GND
Frequency 50Hz or 60Hz, Nominal
Waveform Sinewave
Main Mode Overload
>200% for 5 cycles; 151 - 200% for 1 second; 131-150% 10 seconds;
105 - 130% 1 minute
Battery Parameters
Type Valve-regulated, non-spillable, lead acid
Quantity x V 20 x 12V
Battery Mfr. / Part # CSB HR1234R or Panasonic UP-RW1245
Backup Time See Table 11
Recharge Time (Internal Batteries) 3 hr. to 90% capacity after full discharge into 100% load
Bypass Protection Limits
Maximum Bypass Current 50A
Disable Bypass Operation If input voltage exceeds ±10% of the nominal voltage
Re-Enable Bypass Operation If input voltage returns to within ±8% of nominal output voltage
Disable Bypass Operation When the input frequency prevents synchronous operation
Environmental
Operating Temperature, °F (°C)
32 to 86 (0 to 30) with 0.9 pf
86 to 104 (30 to 40) with 0.8pf
Storage Temperature, °F (°C) 5 to 122 (-15 to 50)
Transportation, °F (°C)
Relative Humidity 0-95% non-condensing
Operating Elevation Up to 3281 ft (1000m) at 80°F (27°C) without derating
Audible Noise <55 dBA at 3.3ft (1m) from rear; <50 dBA at 3.3ft (1m) from front or sides
Agency
Safety UL 1778, c-UL
RFI/EMI FCC Part 15, Subpart B, Class A
Surge Immunity IEC/EN 61000-4-5, ANSI C62.41 (for North America)
Transportation ISTA Procedure 1B