Liebert NfinityTM Power Supply User Manual


 
Installation
13
2.3.2 Connecting to External Panel Boards
The following instructions are also shipped attached to the rear of the unit.
INPUT CABLING AND PROTECTION
Table Below Applies to 4-16kVA Scalable Systems:
Stand-alone UPS or
UPS equipped with a Maintenance Bypass Cabinet
Max. System
Load Rating
Input Voltage – 200/210VAC
Max. Current
in UPS mode
Recommended
Input Protection
Circuit Breaker
4kVA 18 amps 50 amps
8kVA
36 amps 50 amps
12kVA 53 amps 75 amps
16kVA
70 amps 100 amps
Terminal
Block
Details
Maximum: 35mm
2
(2AWG)
Minimum: 16mm
2
(6AWG)
Torque Rating: 2.5-3.0Nm (22-26in/lbs)