Liebert GXT2-6000 RT208 Power Supply User Manual


 
System Description
6
3.5 DC to DC Converter
The DC to DC converter utilizes energy from the battery system and raises the DC voltage to the opti-
mum operating voltage for the inverter. This allows the inverter to operate continuously at its opti-
mum efficiency and voltage, thus increasing reliability.
3.6 Battery
The UPStation GXT2-6000RT208 utilizes valve-regulated, nonspillable, flame retardant, lead acid
batteries. To maintain battery design life, operate the UPS in an ambient temperature of 68°F to 77°F
(20°C to 25°C). Optional external battery cabinets are available to extend battery run times.
3.7 Dynamic Bypass
The UPStation GXT2-6000RT208 provides an alternate path for utility power to the connected load in
the unlikely event of a UPS malfunction. Should the UPS have an overload, overtemperature or UPS
failure condition, the UPS automatically transfers the connected load to bypass. Bypass operation is
indicated by an audible alarm and illuminated amber Bypass indicator (other indicators may be illu-
minated to indicate the diagnosed problem).
The user may manually transfer the connected load from the inverter to bypass by pressing the
Standby button once.
NOTE
The bypass power path does NOT protect the connected equipment from disturbances
on the utility supply.