Specifications
42
ENVIRONMENTAL
Operating Temp +32°F to +104°F (0°C to +40°C)
Storage Temp +5°F to +122°F (-15°C to +50°C)
Relative Humidity 0% to 95%, non-condensing
Operating Elevation Up to 10,000 ft. (3000m) at 104°F (40°C) without derating
Storage Elevation 50,000 ft. (15,000 m) maximum
Audible Noise
<55 dBA, at 1 meter from the rear
<50 dBA, at 1 meter from the front or sides
AGENCY
Safety UL 1778, c-UL Listed (Suitable for computer room applications)
RFI/EMI FCC Part 15, Subpart B, Class A
Surge Immunity IEEE/ANSI C62.41 Category A & B
Transportation ISTA Procedure 1A
Table 9 Battery specifications
Model Number GXT2-144BATKIT
DIMENSIONS in (mm)
Shipping W x D x H in. (mm) 13.4 x 27.2 x 13.4 (340 x 690 x 340)
WEIGHT lbs (kg)
Unit 79 (35.8)
Shipping 84 (38.1)
Type Valve-regulated, non-spillable, flame retardant, lead acid
Quantity x V x Rating 12 x 12V x 9.0 AH
Battery Mfg / Part # Yuasa / REW 45-12 FR
Back-Up Time See Table 7 - Battery run times
Recharge Time 6 Hours to 90% capacity after full discharge into 100% load
Table 10 Power distribution box specifications
Model Number PD-HDWR
Amp Rating 24 Amps
Input Power Connection 4-Wire Hardwired, 8-10AWG
Output Power Connection 4-Wire Hardwired, 8-10AWG
Input Branch Circuit Breaker 30 Amp, Supplied by User
Model Number PD-HDWR-MBS
Amp Rating 24 Amps
Input Power Connection 4-Wire Hardwired, 8-10AWG
Output Power Connection 4-Wire Hardwired, 8-10AWG
Includes: Manual Bypass Switch with Indicator Lamps
Input Branch Circuit Breaker 30 Amp, Supplied by User
Model Number PD-001
Amp Rating 24 Amps
Input Power Connections L14-30P on 10 foot cord
Output Power Connection
L1-L2-G (1) L6-30R on a 300mm cord
L1-L2-N-G (1) L14-30R on a 300mm cord
L1-N-G (2) 5-15/20R, T-type, receptacles with (2) 20A circuit breakers
L2-N-G (2) 5-15/20R, T-type, receptacles with (2) 20A circuit breakers
Includes: Manual Bypass Switch with Indicator Lamps
Input Branch Circuit Breaker 30 Amp, Supplied by User
Table 8 UPS specifications (continued)
Model Number GXT2-6000RT208