8.8 Battery Tab
Factory default settings illustrated.
The boxes on the right show the available options using the drop-down selection boxes.
8.8.1 Low Battery Time Warning
The UPS will estimate remaining operating time when on batteries. A low battery alarm is activated
if the estimated time reaches the Low Battery Time. This may be changed to any value from 2 to 30
minutes.
8.8.2 Auto Battery Test Time
The UPS performs an automated battery test periodically, if enabled. The user may also select time
periods of 7, 14, 21 and 28 days.
8.8.3 Battery Cabinets Number
If additional batteries are attached to the UPS, accurate battery runtime estimates are possible if the
battery number and type of batteries are entered here. The new UPS models are designed to operate
with up to four external battery packs or four long runtime battery packs (not currently available).
8.8.4 Auto Battery Test
In some applications it may be preferable to disable the automated, periodic battery test. Click on the
box to remove the check mark and disable the periodic battery test.