MGE UPS Systems 4000 RT Power Supply User Manual


 
34008030EN/AA - Page 26
4. Access to measurements and personalisation data
4.4 UPS set-up
Local settings
Output settings
ON/OFF settings
Function Factory setting Options
Language English French, German, Italian, Portuguese, Spanish
Date / Time Format International
(DD-MM-YYYY/HH :MM)
US (MM-DD-YYYY/HH:MM AM/PM)
Date / Time Change GMT + 1
(Continental Europe)
MM-DD-YYYY/HH :MM adjustable
Audible Alarm Yes No
Function Factory setting Options Comments
Output Voltage 230 V 200 V / 208 V / 220 V /
240 V / 250 V
Freq Converter Disable Enable
Output Frequency 50 Hz 60 Hz User selectable under frequency-
converter mode
Eco Mode DisablE Enable See glossary
Slew Rate 1 Hz / sec. 0.5 Hz / sec.
Bypass Transfer
If bypass Ac nok?
Yes No Transfer to bypass if Normal AC
source is out of tolerance
Interrupt Time 10 ms 20 ms, ...... , 200 ms Break time calibration during load
transfer on Normal AC source out of
tolerance
Overload Prealarm 105 % 40 %, 50 %, 70 % Alarm if threshold is overrun
Redundancy Mode No Yes On parallel sequence : Alarm if
redundancy loss
Function Factory setting Options Comments
Cold Start Disable Enable Start on battery
Forced Reboot Enable Disable Enables automatic restart of the
system even if Normal AC source is
restored before the end of the
shutdown sequence
Auto Restart Enable Disable UPS restarts automatically when
Normal AC source is restored
Energy Saving Disable Enable Automatic shutdown on battery if
output load level < 10 %
Sleep Mode Enable Disable
Remote Command Enable Disable Enables consideration of shutdown
or restart orders from software to be
authorised