MGE UPS Systems EX-5, EX-7, EX-11RT Power Supply User Manual


 
Table 5-7: Efficiency on ECO mode (all kinds of load) and batteries fully charged.
5.6 Heat Rejection
Table 5-8: Full load heat rejection in BTU’s/hr.
System Operation Mode
On-line On Battery
5kVA 1350 1861
7kVA 1654 2280
11kVA 3033 3723
5.7 Environmental Characteristics
The operating temperature is 0 to 40°C (8 hours at 45°C), however optimum operation is within the +20 to
+25°C range and at 5-95% humidity, non-condensing at altitude up to 3280ft without de-rating.
The storage temperature: -20 to 40°C. Humidity: 5-95%, non condensing.
Battery backup time is adversely affected by high and low temperatures. It is significantly reduced at tempera-
tures under 10°C. Above 25°C, battery service life is cut in half every 10°C. Above 40°C, battery manufacturers
no longer guarantee operation due to the risk of thermal runaway.
Air enters through the front air vent grills and exits through the back. Always keep air vent grills unobstructed.
kVA / kW 25% 50% 75% 100% Output load percentage
5kVA /
4kWatts
96
95
97
96
96
96
97
96
Output: 220 / 230 / 240 Volts
Output: 200 / 208 / 250 Volts
7kVA /
4.9kWatts
96
95
97
96
96
96
97
96
Output: 220 / 230 / 240 Volts
Output: 200 / 208 / 250 Volts
11kVA /
8kWatts
96
95
97
96
96
96
97
96
Output: 220 / 230 / 240 Volts
Output: 200 / 208 / 250 Volts
EX 5/7/11RT Systems
Appendix5 — 4 86-86000-00 B00