PROFIBUS Communications Handbook Tag Addresses
2408
f
and 2404
f
PROFIBUS Communications Handbook 8-3
Controller
Run Tab
Tag
Display Parameter Description Addres
s
Current program running
(active prog no.)
22
Program Status
1: Reset
2: Run
4: Hold
8: Holdback
16: Complete
23
Programmer setpoint 163
Program cycles remaining 59
Current segment number 56
Current segment type
0: End
1: Ramp (Rate)
2: Ramp (Time to target)
3: Dwell
4: Step
5: Call
29
Segment time remaining in secs 36
Segment time remaining in mins 63
Target setpoint (current
segment)
160
Ramp rate 161
Program time remaining 58
Fast run
0: No
1: Yes
57
Logic 1 output (current program)
0: Off (applies to all 8 logic
outputs)
1: On (applies to all 8 logic o/ps)
464
Logic 2 output (current
program)
465
Logic 3 output (current
program)
466
Logic 4 output (current
program)
467
Logic 5 output (current
program)
468
Logic 6 output (current
program)
469
Logic 7 output (current
program)
470
Logic 8 output (current
program)
471
Segment synchronisation
0: No
1: Yes
488
Flash active segment in lower
display
284
Advance Segment Flag 149
Skip Segment Flag 154
Program Logic Status 162
Controller
Alarm Tab
Tag
Display Parameter Description Address
Alarm 1setpoint value 13
Alarm 2setpoint value 14
Alarm 3setpoint value 81
Alarm 4setpoint value 82
Alarm 1 hysteresis 47
Alarm 2 hysteresis 68
Alarm 3 hysteresis 69
Alarm 4 hysteresis 71
Loop break time
0: Off
83
Enable diagnostic messages
0: No Diagnostics
1: Diagnostics
282
Acknowledge All Alarms 274
Controler
Autotune Tab
Tag
Display Parameter Description Address
Autotune enable
0: No Tune
1: Tune
270
Adaptive tune enable
0: No Adaotive Tune
1: Tune
271
Adaptive tune trigger level 100
Automatic droop
compensation (manual reset)
0: Manual reset
1: Calculated
272