Mitsubishi Electronics MIM-A01 Modem User Manual


 
6.2 MIM and Mitsubishi MELSEC FX
The modem may be operated along with MELSEC FX in two ways: As GSM modem for "FX
Messenger" or as modem for FX remote access.
6.2.1 MIM-G01 and FX Messenger
In order to connect the MIM-G01 to a FX1S Messenger, the modem must be initialized with the
following init string, which sets the handshake mode (no handshake will be executed) and the
transmission speed (19200 bps).
MIM-G01
AT+IFC=0,0;+IPR=19200;&W
The modem is to be connected to the RS232-BD of the FX Messenger via standard RS232
cable. Detailedinformation onconfiguring the FXmessenger is tobe foundin the FXMessenger
Manual.
6.2.2 MIM for FX Remote Access
Detailed information on correct modemselection and the necessary parameters are to be found
within the Mitsubishi Manuals at http://www.mitsubishi-automation.com
GX IEC Developer – Reference Manua Art. No. 043596
FX Communications User Manual Art. No. 070143
GX Developer – Operating Manual Art. No. 160262
When using FX along with MIM-G01, we do recommend this init string:
AT+WRST=1,"024:03";+IPR=9600;+IFC=0,0;+ICF=5,1;E1V1Q1S0=2&W
The init string recommended for using the FX along with the MIM-A01, is as follows:
AT%C0"H0E0Q1V1S0=2&D0+K0&W+TFORMAT="7E1";+TBAOD="9600"
6.3 Connection to other Mitsubishi Products
The Industrie-Modemsmay be usedalong withthe Aand Q seriesof MitsubishiPLCs, as wellas
for accessing E-Terminals.
Detailed information on correct modemselection and the necessary parameters are to be found
within the Mitsubishi Manualsat
http://www.mitsubishi-automation.com
as well as well as in the
E-Terminal manuals at
http://www.e-terminals.com.
Configuration MIM and Mitsubishi MELSEC FX
Mitsubishi Industrial Modem 6-5