Nexus 21 A1557 Server User Manual


 
Document Ref: Nex8inst.doc/Rev0 09.07.00 Page 30 of 30 Originator MC Checked by AC__
Device type Type
Code
Condition Panel response Analogue Value Status bits
(210)
Output bits Default cause
and effect
Comments
XP95 heat
detector high
6 Quiescent
Fire
Alert
Fault
None
Fire
Alert
Data fault
AV = 8 to 44
AV = 55 to 127
AV = 45 to 54
AV = 0 to 7
Echo
output bits
0 = remote LED
1 = self test
2 = LED
Bit 0 and bit 2
set when device
is in fire
See note 1.
Series 90
callpoint/
callpoint monitor
7 Quiescent
Alarm
Fault
None
Fire
Fault
AV = 16
AV = 64
AV = 4
L10
L01
L10
0 = remote LED
1 = self test
2 = LED
Bit 2 set when
in fire
Input bit 2
confirms LED
operation and is
represented by L
XP95 callpoint 7 Quiescent
Alarm
Fault
None
Fire
Fault
AV = 16
AV = 64
AV = 4
L10
L01
L10
0 = remote LED
1 = self test
2 = LED
Bit 2 set when
in fire
Input bit 2
confirms LED
operation
XP95 Mini
switch monitor
with interrupt
7 Quiescent
Alarm
Fault
None
Fire
Fault
AV = 16
AV = 64
AV = 4
L10
L01
L10
0 = remote LED
1 = self test
2 = LED
Bit 2 set when
in fire
Input bit 2
confirms LED
operation
XP95 USA mini
priority switch
monitor
7 Quiescent
Alarm
Fault
None
Fire
Fault
AV = 16
AV = 64
AV = 4
L10
L01
L10
0 = remote LED
1 = self test
2 = LED
Bit 2 set when
in fire
Input bit 2
confirms LED
operation
Notes:
The analogue thresholds for analogue detectors can be changed for both fire and alert. See the installation and commissioning manual for details.
On the S90 3-way analogue unit, either the analogue value or logic inputs can raise alarms. The analogue thresholds can also be changed for fire and
alert on this device. See the installation and commissioning manual for details.
The number of devices with LEDs operated is limited to eight per loop.
If a device has more than one condition active then only the highest level event will be reported although lower level alarms may be present on the
display. For example, if a smoke detector enters an alert condition this will be indicated on the panel. If the device subsequently enters a fire
condition the alert will clear but the alert LED will become steady to indicate the event occurred.