Nx Networks NX series Power Supply User Manual


 
12(86)
Receipt of shipment
3
3. RECEIPT OF SHIPMENT
The NX frequency converters have undergone rigorous tests and quality checks at the factory
before delivery. However, after unpacking the product, check that no signs of transport damages
are to be found on the product and that the delivery is complete (compare the type designation of
the product to the code below, Figure 3-1.
Should the drive have been damaged during the shipping, contact the carrier and or distributor.
If the delivery does not correspond to your order, contact the supplier immediately.
3.1 Type designation code
Figure 3-1. NX type designation code
3.2 Storage
If the frequency converter is to be kept in store ensure that the ambient conditions are acceptable:
Storing temperature –40…+70
°
C
Relative humidity <95%, no condensation
NXS 0000 V 3 5
Motor current (low overload)
0007 = 7 A, 0022 = 22 A, 0205 = 205 A etc.
Voltage (3-phase):
2 = 208–240Vac, 5 = 380–500Vac, 6 = 525–690Vac (All 3-phase)
Control panel:
A = standard (alpha-numeric)
B = neutral (no local control panel)
C = special (special switches, potentiometer etc.)
D = dummy panel
EMC emission level:
H = fulfils standard IEC 61800-3 (Am 1 industrial level), 1st environment
restricted distribution, 2nd environment
T = fulfils standard IEC 61800-3 (Am 1 commercial level) for IT networks
C = fulfils standards EN50081-1, -2 and EN61800-3
Product series: NXS = standard, NXP = high-performance
Brake chopper
0 = no brake chopper
1 = internal brake chopper
2 = internal brake chopper and resistor
A 2 C 1
Enclosure class:
0 = IP00, 2 = IP21 (Nema 1), 5 = IP54 (Nema 12)
Phase:
1 = 1-phase, 3 = 3-phase
Voltage