4. UPS functions
Setting for beeper sound in the event of power failure, etc. (setting switch 1 )
Factory setting: OFF
OFF: The beeper sounds when an alarm is necessary.
ON: The beeper does not sound for backup operation or battery replacement. The beeper sounds for
other errors (connection capacity exceeded, operation error, etc.).
ON DIP
1 2 5 6 7 83 4
OFF: Automatically starts when power is restored.
After a power failure occurs and the unit shuts down using the shutdown software or contact signal(BS
signal), the unit automatically starts and begins to output when the commercial power is restored.
ON: Does not automatically start when power is restored.
After the unit is shut down with the UPS monitoring software or contact signal (BS signal), it does not
start up when commercial power is restored. Startup is performed by turning the power switch OFF
once, and then back ON again.
1 2 53 4 86 7
ON DIP
Auto startup setting after recovery from power failure (setting switch 2 )
Factory setting: OFF
No.
1
2
3
4
5
6
7
8
OFF side
ON side
* In the factory settings, everything is OFF.
Function to set
Setting for beeper sound in the
event of power failure, etc.
Auto startup setting after
recovery from power failure
Setting for whether or not to
perform battery test
Auto startup mode setting
BS signal valid range setting
Beeper does
not sound
Do not perform
auto startup
Do not perform
test
Mode B
---
Valid only during
Battery Mode
Beeper sounds
Perform auto startup
Perform test
Mode A
Always valid
Setting switch function list