88
Reference
References
A. Specifications
Frequency 50/60Hz ± 4Hz
Maximum current 7.4A 16A
Phase Single-phase, two-wire
Input plug shape NEMAL6-15P NEMAL6-20P
Input protection Reset-type overcurrent protection device
Input protection capacity 10A 20A
Output
Allowable connection capacity *1
1000VA/700W 3000VA/2100W
Voltage (effective value) *2
Peak voltage value 200V mode: AC282V ± 6% 220V mode: AC310V ± 6%
(In Commercial Power Mode)
230V mode AC324V 6% 240V mode AC338V 6%
Peak voltage value 200V mode AC282V 6% 220V mode AC310V+6%/-10%
(In Battery Mode) 230V mode AC324V+6%/-10% 240V mode AC338V+6%/-12%
Frequency 50/60Hz ± 1Hz
Phase Single-phase, two-wire
Output waveform
Sine wave
Waveform distortion rate 200V mode: 6% max. 220V mode: 10% max.
(Rectified load, at rated output)
230V mode: 10% max. 240V mode: 12% max.
Number of output receptacles IEC60320 C13 : 3 pcs. IEC60320 C19 : 1 pcs. C13 : 5 pcs.
Terminal block: 2 lines Terminal block: 2 lines
Power failure switching time Uninterrupted
Commercial direct shipment
(switching time)
4msec. max.
Backup time *3
Minimum 5 minutes
Battery Type Compact sealed lead battery
Sealed lead battery life expectancy
4 to 5 years (long operating life) *At ambient temperature of 20°C
Battery capacity (V/Ah) (x Quantity)
12V DC/ 7.2 Ah (x 3) 12V DC/ 9 Ah (x 6)
Charging time 8 hours *4
Environment
Operating ambient temperature
0 to 40°C (during operation)/ -15 to 50°C (during storage)
Operating ambient humidity
25 to 85%RH (during use)/10 to 90%RH (during storage)
Dimensions 145 x 395 x 224 (±1) mm *5 213 x 537 x 432 (±1) mm *6
Weight of unit
Approx. 15.5 kg Approx. 35 kg
Internal power
consumption (max.)
50W (100W max.) 55W (155W max.)
*7
Noise regulation
(compliance standard)
VCCI Class A
Safety standard compliance
UL/CE
Noise 50 dB max. 55 dB max.
BU1002SW BU3002SW Type
200V mode AC200V ± 3%
220V mode AC220V ± 3%
230V mode AC230V ± 3%
240V mode AC240V ± 3%
Method Operation method Full-time inverter supply method
Connectable devices
PC, display, and peripherals
Input Rated input voltage 200 to 240V ± 10%
Allowable voltage range
AC145±4 to 276±4V (with 85% or less connection load)
AC170±4 to 276±4V (with 85% or more connection load)
*1: Make sure that both the VA value and the W value of the load capacity connected to the UPS are within the range specified here.
*2: Check the operation beforehand if the unit is used in any mode other than “200V AC mode”. In some cases, the maximum voltage
of output in Battery Mode may be lower than the maximum voltage in usual operation (commercial power supply).
*3: The backup times shown here are for when rated load is connected, at 20°C, and for initial characteristics.
*4: When an additional battery unit is connected, the charging time is 24 hours.
*5: The height includes the 13-mm height of the rubber feet.
*6: The height includes the 56mm height of the casters.
*7: 170W max when and additional battery unit is connected.