● Remote ON/OFF Signal
Remote ON/OFF signals can be used to start and stop
the UPS, by using either an externally connected con-
tact or the ON/OFF status of the open collector circuit. To
use this function, turn on the Power Switch of the UPS.
(Note: When there is no AC power supply, it is not pos-
sible to start up UPS by the remote ON/OFF signals even
though cold start is set ON.)
Connection terminals are at contact signal connector pins
6 ,7 and the remote ON/OFF connector.
3. Items that can be set using the contact signal card
Please make a cable to connect to the system by yourself.
See also
"8. Example of the use of the Contact Signal circuit" ➛ Page 81
■Setting the switches
Jumper setting
s
(8 digits)
DIP switches
(3 digits)
External contact Operate
Open Start
Close Stop
Caution
After changing the setting switch, disconnect the AC input plug, wait until the
status indicator is completely OFF, and then reinsert the AC input plug.
● The setting switch changes do not become valid until the AC input plug is reinserted.
By using the switches of contact signal card, set the item below.